Hello! Welcome to the official website of Shenzhen Lilutong Technology Industrial Co., Ltd.!

UL1424 fire alarm cable

Advisory Service
  • Product Model, Production Range
  • Product Usage
  • Product Structure
  • Product Performance
  • Product Advantage (Selling Point)
  • Product Code Identification
  • Fire alarm line model: FPL FPLR
    FAS FAS90 FAS105
    Power line: CL2 CL3 CL2R CL3R
    Serial number product type Core number or logarithm Specifications
    1 Alarm lineFPL、FPLR  2~8core 26-10AWG
    2 Power lineCL2、CL3、CL2R、CL3R 26-6AWG

  • Fire-proof cables are suitable for high-rise buildings, entertainment places and many high-quality and high-security building projects. They are used for power supply lines in fire-fighting system, such as fire elevators, fire pumps, fire alarms, smoke exhaust systems, emergency lighting, fire hazard zones, high-temperature occasions and facilities requiring special safety.

  • Central conductor: Solid or stranded soft annealed copper, should be circular, in line with ASTM B 3 requirements.
    Multi-stranded conductor: 19-10AWG maximum strand length is 20 times stranded outer diameter; 26-20AWG maximum strand length is 30 times stranded outer diameter.
    Insulator: flame retardant PVC
    Shielding layer: Aluminum foil shielding + braided copper wire shielding (optional)
    Ground wire: copper wire consistent with the central conductor
    Packing tape: PS wrapping or mica wrapping (optional)
    Tearing rope: Nylon rope
    Sheath: Flame retardant PVC sheath, color: (optional)
  • ●Physical and mechanical properties: the tensile strength of insulation is not less than 10.3 MPa, the elongation at break is not less than 100%; the tensile strength of sheath is not less than 10.3 MPa, and the elongation at break is not less than 100%; it meets the test requirements of UL1581 50.182.
    ●Minimum bending radius: 10 x D, minimum bending diameter < 12.5 MM at - 15 C
    ●Operating voltage: 300/300V
    ●Test voltage: 1500V
    ●Use temperature range 75 ~90 ~105 ~C (optional)
    ●Fire-resistant and flame-retardant grade conforms to UL1424 standard
    FPLR, CL2R, CL3R fire test meets UL1666 requirements
    FPL, CL2, CL3 fire test meets UL1581 vertical combustion VW-1 or CSA FT4/EE-1202 combustion test requirements.

  • ●Products passed UL1424, UL13 certification products passed UL1424, UL13 certification
    ● Wire materials meet the requirements of low smoke, halogen-free, flame retardant, fire-resistant and green environmental protection.
    ●Low smoke halogen-free cables and wires produce very small amount of smoke in the case of flame combustion, and the released gas does not contain halogen elements. When a fire occurs, it can greatly reduce the harm of environmental protection cables to instruments, equipment and human body.
    ●Wire has high flame retardancy, strong self-extinguishing property and extinguishing characteristic when it leaves fire.
    ●Long service life, inorganic insulating material, high temperature resistance, and not easy to aging, his life is many times longer than that of organic insulated cables? In normal working conditions, its life can be the same as that of buildings.

  • Editing...

Copyright © 2018 Shenzhen Lilutong Technology Industrial Co., Ltd All rights reserved © Copying is prohibited without permission    ICP:
Technical Support: 南(nán)博網